Depth of discharge (DoD) and battery lifetime

· 5 min read ·

Understand what DoD is, why shallower discharges give more cycles and how much energy a battery delivers over its life, and try the values in the calculator.

What depth of discharge is

The depth of discharge (DoD) says how much of the battery’s capacity you use in one cycle. If a 10 kWh battery delivers 8 kWh before being recharged, the discharge was 80%.

8 kWhenergy taken in the cycle÷10 kWhnominal capacity=80%depth of discharge

Why shallow discharges last longer

Each cycle wears the battery, and wears it more when it is deeper. The number of cycles a battery can take falls sharply with the depth of discharge, and the drop is steeper for lead-acid.

Lithium (LiFePO4) life cycles by DoD (typical, illustrative values)

10% DoD10,000
30% DoD8,000
50% DoD6,500
80% DoD4,000
100% DoD2,500

Lead-acid life cycles by DoD (typical, illustrative values)

10% DoD3,000
30% DoD1,800
50% DoD1,000
80% DoD450
100% DoD250

Calculate your battery’s life

Choose the type, the discharge of each cycle and the nominal capacity. The calculator interpolates the table and shows the cycles, the years (at one cycle per day) and the total energy the battery delivers over its life.

Interactive

Discharge versus lifetime

Choose the battery type and the depth of discharge of each cycle. The typical table shows how many cycles, how many years and how much total energy the battery delivers.

4,000estimated life cycles
11years equivalent to 1 cycle per day
16,000 kWhidealized accumulated energy over its life

Typical, illustrative values, interpolated. The manufacturer’s datasheet prevails. The calculation ignores calendar ageing and capacity loss.

More cycles is not always more energy

Shallow discharges give more cycles, but each cycle delivers less energy. What matters is the total energy delivered over its life (capacity × DoD × cycles, an idealized estimate that ignores capacity loss over its life). For a 5 kWh lithium battery:

Total energy delivered by a 5 kWh lithium bank, in kWh

30% DoD (8,000 cycles)12,000
50% DoD (6,500 cycles)16,250
80% DoD (4,000 cycles)16,000
100% DoD (2,500 cycles)12,500

In the illustrative table used here, the range between 50% and 80% delivers the most accumulated energy. Raising the depth of discharge to 100% reduces total energy. In this example, operating at 30% DoD also reduces the calculated accumulated energy; the real choice also depends on the reserve you want and the operating conditions.

Using DoD in sizing

  1. 1
    Set the energy per day

    The home needs 5 kWh from the battery per day.

  2. 2
    Choose the design DoD

    With lithium at 80%, the nominal capacity is 5 ÷ 0.8 = 6.25 kWh. At 50% it would be 10 kWh.

  3. 3
    Estimate the life

    At 80% that is 4,000 cycles: at one cycle per day, about 11 years (arithmetic equivalent at one cycle per day, ignoring calendar ageing) and 20,000 kWh delivered, as an idealized estimate.

Do

  • Set the discharge cut-off on the inverter to match the chosen DoD
  • Use the manufacturer’s datasheet, which gives the cycles per DoD
  • Remember that life also depends on temperature and current
  • Leave a reserve for autonomy: see how to calculate backup time

Avoid

  • Discharge to zero often
  • Leave the battery discharged for long periods
  • Compare batteries by nominal capacity alone
  • Buy extra capacity that will never be used

Draw it in Editor Solar

This is Editor Solar itself, already loaded with the diagram from this article. Move the equipment, edit labels, connect new parts and export to PNG, SVG or PDF. It is free and runs right in your browser.

A 6.25 kWh bank used at 80% discharge to supply 5 kWh per day.

Try it: Change the DoD to 50% and redo the bank’s nominal capacity. Note how many extra kWh you would need to buy.

Ready-made templates: see all diagram templates

Open this diagram in the full editor ↗

Keep learning

How to connect batteries in series and in parallelLearn what happens to voltage, current and capacity when you connect batteries in series, in parallel or both, with examples and practical precautions.5 min read → On-grid, off-grid or hybrid: which solar system to chooseCompare the three types of photovoltaic system: how they work, what happens during a power outage, relative costs and when each one makes the most sense.5 min read → Solar panels in series and in parallel: understanding stringsHow series and parallel connections change module voltage and current, what a string is, how it relates to the MPPT and why cold weather matters.6 min read → PV system protection: SPDs, breakers, fuses and combiner boxesThe devices that protect people and equipment in a solar installation, from string fuses to the RCD in the board, and where each one goes in the diagram.6 min read → Battery bank backup time: how to estimate it in kWh and hoursLearn to calculate the stored energy, the energy you can actually use and how many hours a battery bank can run your home loads, with a step-by-step example.5 min read → How to read a solar panel label (datasheet)Pmax, Voc, Isc, Vmp, Imp, STC, NOCT and temperature coefficients: understand every number on a PV module label and what it is used for in the design.5 min read → How to estimate home energy use from your electricity billLearn to read the kWh on your bill, work out daily use and average power, and check it by adding up your appliances before sizing a solar system.6 min read → How many solar panels do I need? The calculation step by stepWork out the number of panels from monthly consumption, peak sun hours and system efficiency, with a complete example and an interactive calculator.5 min read → How to choose the right solar inverter sizeUnderstand the DC/AC ratio, why the inverter can be smaller than the panels and how to reach the right standard size, with an interactive calculator.5 min read → W, kW, Wh, kWh and Ah: solar energy units explainedTell power from energy, understand each unit and learn the calculations that link panels, inverter and battery, with everyday examples.5 min read → Solar system losses and the performance ratio (PR)Understand what reduces a system’s energy output: temperature, soiling, cables, shading and inverter. See the performance ratio and adjust the losses.5 min read → How many panels per string? Voc, Vmp and temperature in practiceSee how to work out the minimum and maximum panels per string from Voc, Vmp and temperature in four example scenarios, and test your own data in the calculator.6 min read → Roof orientation and tilt: how much does output change?Find out how much roof direction and tilt change solar output, with numbers for each case and a calculator to test your own roof.5 min read → Shading: effect on strings, optimizers and microinvertersUnderstand why the shade on a single panel can reduce the string’s output, what bypass diodes do, and when optimizers and microinverters are worth it.5 min read → Lithium (LiFePO4) or lead-acid: which battery to chooseCompare LiFePO4 lithium and lead-acid in usable capacity, lifetime, cost per kWh delivered and care needs, and see which one suits each use best.5 min read → 12 V, 24 V or 48 V battery: which voltage for the bankSee why the bank voltage changes the current, the cable size and the loss, and choose 12 V, 24 V or 48 V by system power. A calculator is included.5 min read → What a BMS does and why communication with the inverter mattersLearn what a lithium battery BMS does, how it talks to the inverter and what changes with or without communication. Simulate its limits in the calculator.5 min read → String inverter, microinverter or optimizer: a practical comparisonCompare the three conversion architectures: how each handles shade, multi-slope roofs, monitoring, cost and expansion. See the difference in the calculator.5 min read → How a hybrid inverter works, step by stepUnderstand the ports of a hybrid inverter, the order in which it decides where each kW goes and its operating modes. Follow the energy flow in a calculator.5 min read → Home backup: which loads to put on the essential circuitSee how to choose the loads for the essential circuit of a battery system, respect the inverter limit and estimate the hours of backup, in a calculator.5 min read → A generator as backup in an off-grid system: how the ATS worksUnderstand what a generator is for in an off-grid system, what the ATS prevents, the start-up sequence and how to size it in the calculator.6 min read → Grounding in PV systems: what each connection is forWhat each earth connection does in a solar system: structure, inverter, SPDs and busbar. A guide to concepts; exact rules come from the local standard.6 min read → Voltage drop and cable size: how to choose and why it mattersLearn to calculate a cable’s voltage drop and the minimum cross-section for it, why current capacity is another criterion and how to check the standard.6 min read → The string box: what is inside and when you need oneSee what a string box contains, when each string needs a fuse and how to check it with the module current, in a calculator with a complete example.5 min read → How to read a solar single-line diagram: symbols and energy pathLearn to read a solar single-line diagram: what each block means, how to follow the energy from the panels to the grid and what to check in each section.6 min read →