How many panels per string? Voc, Vmp and temperature in practice
See how to work out the minimum and maximum panels per string from Voc, Vmp and temperature in four example scenarios, and test your own data in the calculator.
Temperature changes the voltage
This article applies, in complete examples, what solar panels in series and parallel explains: the number of panels in a string has a minimum and a maximum, and both depend on temperature. In the cold the panel voltage rises; in the heat it falls.
That is why the calculation uses the worst case for each limit: the highest possible voltage (cold) against the inverter limit, and the lowest possible voltage (heat) against the start of the MPPT range.
The data that goes into the calculation
Panel Voc and Vmp
datasheetVoc is the no-load voltage; Vmp is the voltage at the maximum power point. Both are given at 25 °C, under test conditions.
Temperature coefficients
datasheetIn %/°C. Voc usually has about −0.27 %/°C and Vmp about −0.35 %/°C: Vmp varies more.
Site temperatures
climateThe lowest air temperature (a cold dawn) for Voc, and the hot cell temperature, well above the air, for Vmp.
Maximum voltage and MPPT
inverterThe absolute input limit, which Voc must never exceed, and the range in which the inverter tracks maximum power.
The two calculations
With panels of 49.5 V Voc and 41.5 V Vmp, a 600 V inverter with an MPPT range of 160 to 550 V, at a site that reaches −15 °C and with cells at 70 °C in summer:
The string can have 5 to 10 panels. In practice choose a value with some margin from both limits, so you do not depend on an extreme day.
Four scenarios
The same panel calls for different numbers depending on the climate and the inverter. Here is the maximum number of panels in each case:
Test your own numbers
Replace the data with that of your panel’s and inverter’s datasheets and with your site’s temperatures. The calculator shows the voltage at each extreme, the panel range and whether the chosen number meets the stated voltage limits.
Common mistakes
Do
- Use the site’s lowest temperature for Voc and the hot cell for Vmp
- Round the maximum down and the minimum up
- Use the Vmp coefficient from the datasheet, not only the Voc one
- Confirm the limits with the inverter manufacturer
Avoid
- Add up the voltages at 25 °C and stop there
- Push the Voc right up to the inverter limit: a cold morning may exceed it
- Forget that the cell heats up well above the air temperature
- Mix different panels in the same string
Draw it in Editor Solar
This is Editor Solar itself, already loaded with the diagram from this article. Move the equipment, edit labels, connect new parts and export to PNG, SVG or PDF. It is free and runs right in your browser.
Try it: Change the number of panels to 11 and redo the cold Voc calculation: does the string still respect the inverter’s 600 V? Write the result in the diagram text.